Return watt relay

Walcher GmbH & Co. KG
Zum Lingeshof 3
36124 Eichenzell
Tel. +49 6659 98794-0
Fax. +49 6659 98794-44
E-Mail: info@walcher.com

Return watt relay WA-RW 140 / WA-RW 141

0

The setting values are altered by removing the plastic caps by means of a screwdriver.

Important: If the "reverse" power trimmer is turned anticlockwise as far as it will go, the return power relay responds because this is the test setting.

The luminous diode signalizes the existing reverse power virtually without any delay.

If the return watt relay responds at "forwards power" then either the "reverse power" response value has to be set higher for the "k" current transformer connection is to be changed over the "l" current transformer connection.

Connection circuit diagram RW-140 / 141

Technical Data

RW 140

RW 141

Nominal voltage Un

230 V +10%/-15%

Working range

Umax / Umin 250 V/160 V

Nominal frequency

fn 50 - 100 Hz

Nominal current

In 5 A

Response value adjustable

 

(in relation to 5 A nominal) current

3 - 30 %

Adjustable time delay

3 - 15 s

Switching contact, potentialless

 

1 x change-over-swith

 

Switching capacity P max

I max A80 V w 2200 W 2200 W

 

 

Power input in voltage path

 

 

 

 

U max

 

10 A

 

380 V w

 

10 A80 V w 2200 W 2200 W

Power input in voltage path

 

3in current path 8 VA

 

1,5 VA 11 VA

 

1,5 VA

 

Temperature range °C -20 ...+60 -20 ...+60

 

Switching hysteresis approx. 2 %The switching hysteresis can be

 

extendet to customer order. approx. 2 %

 

Dimensions: LxBxH mm 150 x 73 x 115

 

Weight: approx. 0,8 kg

 

Fitting: by means of snap fitting on standard

 

bar or screw fastening.

 

Block circuit diagram Response value Response time

 

When installing the reverse power relay it is important that the "measuring voltage" supply voltage originates from the same phase as that to which the current transducer is connected.

 